Select values
PlantBeat only records what you select in a connection. You do this in the connection wizard: in step 2 you select the values, in step 3 you configure them. Only users with the Administrator role can select values.
Step 2: Select values in the symbol tree
For S7-1200, S7-1500 and Beckhoff, PlantBeat shows the PLC's symbols as a tree. For Siemens, these are data blocks with their names from the TIA Portal, for example "Linie1 (DB1)", plus inputs, outputs and memory bits. For Beckhoff, they are the groups and programs, for example GVL_Demo or MAIN.
- Search variable … finds values by name, for example "Drehzahl".
- Expand all folders or Collapse all folders opens or closes the whole tree.
- HMI-visible variables only hides values that are not enabled for HMI in the TIA Portal. Selected values stay visible.
- Reload reads the PLC's symbols again, for example after a program change.
- Check a value to select it. The number of selected values is shown at the top.
Selected variables are recorded with the default, that is, every value read. You can change this in step 3.
What you can read and write depends on the area: inputs, outputs and technology objects of the S7-1500 are read-only. Memory bits and variables in data blocks are also writable. See S7-1200 and S7-1500 symbolic.
Step 2 in "Legacy" mode: variables by address
For S7-300, S7-400 and LOGO! 0BA8 there is no tree. There you create each variable as a row with Add tag: memory area, offset and type, and for the data block memory area also the name and DB number. How this works is described under S7-300, S7-400 and LOGO! by address.
Step 3: Configure selected variables
On the left is the list of selected values. Use Search variable … to find a value in a long list. Click a value, and its settings appear on the right in two tabs.
Name, unit, scaling
| Field | Meaning |
|---|---|
| Display name | It appears in widgets, history and export. It does not change the recording. Empty means: the name from block and path. |
| Unit | for example °C, bar or rpm |
| Factor and Offset | What is stored: raw value × factor + offset. |
Example: the PLC delivers a temperature in tenths of a degree, so 235 for 23.5 °C. With factor 0.1 and offset 0, PlantBeat shows and stores 23.5.
Note
If you write to a scaled value via a dashboard control, PlantBeat writes the raw value back to the PLC, in the variable's data type.
If another value already has the same display name, the wizard points this out ("Same display name also at: …").
Statistics
Here you define whether and how the value is recorded and how long it is kept. See Statistics per value.
Data blocks with data records
Data blocks from which PlantBeat fetches complete data records with enable flag and done flag appear in the list as a separate entry. See Data records.
Save and change later
Save & continue saves the selection. PlantBeat starts recording right away.
Later, you open the connection on the "Connections" page with Edit. The wizard then starts at the selected variables, without reading the PLC again. To add more values, go Back to step 2.
If you remove a value from the selection, PlantBeat asks for confirmation when saving. Its previously recorded values then no longer appear in widgets, history and export.
Read values only
If PlantBeat should never write to a PLC, check Read only in step 1. Controls and record fetches with a done flag are then blocked for this PLC. Reading, history and alarms continue unchanged.