PlantBeat Federation
In the PlantBeat Federation, each line records on its own PlantBeat Box or PC and sends measured values, alarms and data records to a master. The master shows the values of all lines in dashboards, reports and alarms and passes them on through the Interface (API).
If the network or the master fails, the line keeps recording and catches up afterwards without gaps and without duplicate points.
What you need
| What | Note |
|---|---|
| a master | PlantBeat on Windows (for large federations) or a PlantBeat Box (for small ones). The master can also record itself. |
| the "PlantBeat Master" license on the master | priced by the number of lines. The lines only need their normal license. |
| network from every line to the master | The lines send to the master over HTTPS: port 5211 on Windows, port 443 on the box. The master never opens a connection to a line itself. |
A line belongs to exactly one master. A master cannot also be a line. Federations with several levels are not possible.
Note
On the box, the master needs encrypted access set up under Settings, section "Access & security", card "Secure connection (HTTPS)". On Windows, setup opens port 5211 in the firewall for the "Private" and "Domain" profiles. See Firewall rules.
Where you set what
- On the master: the Federation page in the left sidebar. There you create pairing codes, see the status of each line and manage the lines.
- On the line: Settings, section "Data", card "Federation". There you pair the line, confirm the check code and choose what goes to the master.
Only an administrator can change either. Others see the status ("Only administrators can change anything here — this page shows you the current state.").
Pages in this section
| Page | Content |
|---|---|
| Set up the master and lines | Turn on master mode, pair a line with a pairing code and a check code |
| Certificate and check code | How the line recognizes its master and what to do when the certificate changes |
| Share values | What goes to the master and which values the master may operate |
| Operation and messages | Status of the lines, mail on failure, clock, retention and the messages on the line |
| Decouple and stop master mode | Decouple a line, delete data, run an installation standalone again |
| Replacement device and data backup | What the backup includes and how you replace a line or the master |