Firewall rules

Updated: from version 1.11

These tables list all ports that PlantBeat needs. Only open what you actually use. Network behavior explains what is behind the connections.

Outgoing: always needed

Destination Protocol and port Purpose
IP addresses of your Siemens PLCs TCP 102 Read and write values, also TLS for secured S7-1500
IP addresses of your Beckhoff PLCs TCP 48898 (ADS) Read and write values
license.plantbeat.io HTTPS, TCP 443 License activation, update check, update entitlement
download.plantbeat.io HTTPS, TCP 443 Update packages

Without internet access, PlantBeat keeps running. In that case, the update check and the automatic update entitlement are not available, see Updates and Activate the license.

Outgoing: only when needed

Destination Protocol and port Only if
Web server of your S7 HTTPS, TCP 443 "Texts as in TIA Portal" is set up in the diagnostic buffer
Your mail server SMTP, typically TCP 587 A mail server is entered under "E-mail dispatch (SMTP)"
Your database server TCP 1433 (SQL Server), 5432 (PostgreSQL), 3306 (MySQL / MariaDB) or your port An external data storage is set up
The master in the Federation HTTPS, TCP 443 (Box) or TCP 5211 (Windows) This installation is a line in the Federation
gateway.smartlifebi.com HTTPS/WSS, TCP 443 The connection to a cloud analytics service is set up
tunnel.plantbeat.io SSH, TCP 2222 Remote support access has been requested on the Box
license.plantbeat.io HTTPS, TCP 443 Crash reports or usage data are turned on
Time server (NTP) UDP 123 Always on the Box, for the clock
DNS server UDP and TCP 53 Always on the Box, for names such as license.plantbeat.io

For the map widget in the dashboard, the viewer's browser needs access to tile.openstreetmap.org (HTTPS 443). PlantBeat itself does not call this address.

Incoming: PlantBeat Box

By default, a packet filter is active on the Box. Everything that is not listed in this table is blocked.

Port Purpose
TCP 80 User interface over HTTP and redirect of plantbeat.local
TCP 443 User interface over HTTPS, also for the interface (API) and for receiving data on the master in the Federation
UDP 5353 mDNS, so that plantbeat.local can be found on the network
ICMP Ping
TCP 22 Maintenance access, only from private networks (private address ranges according to RFC 1918 and link-local, the equivalent for IPv6)

From 1.11, port 5210 on the Box can only be reached internally. Open the user interface through http://plantbeat.local or the IP address of the Box, without a port.

Incoming: PlantBeat on Windows

Port Purpose
None by default The user interface only listens on the computer itself, by default at http://localhost:5210 (you can change the port in the setup).
TCP 5211 HTTPS for the Federation master and the interface (API). It only opens when you run the installation as a master or create an API access entry, and only after PlantBeat restarts.

The setup opens port 5211 in Windows Firewall for the "Private" and "Domain" network profiles. If the network is set to "Public", change it to "Private" or "Domain". For a different port, create a firewall rule yourself.

Separate machine network

We recommend a separate network for the PLCs. The PlantBeat Box has two LAN ports for this: one to the machine network, one to the company network. On Windows, use a computer with two network cards. PlantBeat does not forward traffic between the networks.

Next steps