Firewall rules
These tables list all ports that PlantBeat needs. Only open what you actually use. Network behavior explains what is behind the connections.
Outgoing: always needed
| Destination | Protocol and port | Purpose |
|---|---|---|
| IP addresses of your Siemens PLCs | TCP 102 | Read and write values, also TLS for secured S7-1500 |
| IP addresses of your Beckhoff PLCs | TCP 48898 (ADS) | Read and write values |
license.plantbeat.io |
HTTPS, TCP 443 | License activation, update check, update entitlement |
download.plantbeat.io |
HTTPS, TCP 443 | Update packages |
Without internet access, PlantBeat keeps running. In that case, the update check and the automatic update entitlement are not available, see Updates and Activate the license.
Outgoing: only when needed
| Destination | Protocol and port | Only if |
|---|---|---|
| Web server of your S7 | HTTPS, TCP 443 | "Texts as in TIA Portal" is set up in the diagnostic buffer |
| Your mail server | SMTP, typically TCP 587 | A mail server is entered under "E-mail dispatch (SMTP)" |
| Your database server | TCP 1433 (SQL Server), 5432 (PostgreSQL), 3306 (MySQL / MariaDB) or your port | An external data storage is set up |
| The master in the Federation | HTTPS, TCP 443 (Box) or TCP 5211 (Windows) | This installation is a line in the Federation |
gateway.smartlifebi.com |
HTTPS/WSS, TCP 443 | The connection to a cloud analytics service is set up |
tunnel.plantbeat.io |
SSH, TCP 2222 | Remote support access has been requested on the Box |
license.plantbeat.io |
HTTPS, TCP 443 | Crash reports or usage data are turned on |
| Time server (NTP) | UDP 123 | Always on the Box, for the clock |
| DNS server | UDP and TCP 53 | Always on the Box, for names such as license.plantbeat.io |
For the map widget in the dashboard, the viewer's browser needs access to tile.openstreetmap.org (HTTPS 443). PlantBeat itself does not call this address.
Incoming: PlantBeat Box
By default, a packet filter is active on the Box. Everything that is not listed in this table is blocked.
| Port | Purpose |
|---|---|
| TCP 80 | User interface over HTTP and redirect of plantbeat.local |
| TCP 443 | User interface over HTTPS, also for the interface (API) and for receiving data on the master in the Federation |
| UDP 5353 | mDNS, so that plantbeat.local can be found on the network |
| ICMP | Ping |
| TCP 22 | Maintenance access, only from private networks (private address ranges according to RFC 1918 and link-local, the equivalent for IPv6) |
From 1.11, port 5210 on the Box can only be reached internally. Open the user interface through http://plantbeat.local or the IP address of the Box, without a port.
Incoming: PlantBeat on Windows
| Port | Purpose |
|---|---|
| None by default | The user interface only listens on the computer itself, by default at http://localhost:5210 (you can change the port in the setup). |
| TCP 5211 | HTTPS for the Federation master and the interface (API). It only opens when you run the installation as a master or create an API access entry, and only after PlantBeat restarts. |
The setup opens port 5211 in Windows Firewall for the "Private" and "Domain" network profiles. If the network is set to "Public", change it to "Private" or "Domain". For a different port, create a firewall rule yourself.
Separate machine network
We recommend a separate network for the PLCs. The PlantBeat Box has two LAN ports for this: one to the machine network, one to the company network. On Windows, use a computer with two network cards. PlantBeat does not forward traffic between the networks.