Recording
A value is missing from the history
| What you see | What helps |
|---|---|
| "No data in this time range." | Choose a longer time range. Check that the connection is running and that "Record statistics" is on for the value. |
| The value is missing from the selection | The value is not selected, or its statistics are off. Open the connection with Edit, Statistics tab. |
| Older values are missing | Retention has deleted them, see Retention and storage. |
| The value appears in the dashboard but not in the history | Without "Record statistics", PlantBeat shows the value live but does not store it. |
Values that PlantBeat reads through enable and done flag have statistics turned off by default. Turn them on in the Statistics tab if you need them in the history. See Statistics per value.
The values are "frozen"
Read the notice bar at the top of the page:
- Trial mode expired: Without a license, PlantBeat records from a real PLC for 10 minutes. See License.
- Version not covered, license expired or clock set back: PlantBeat no longer connects to real PLCs. See License and Clock and clock code.
If nothing is shown there, check the state of the connection on the Connections page, see PLC connection. Demo connections never count toward trial mode and always keep running.
The history shows a smooth curve instead of every peak
For long time ranges, the history shows a value condensed as the average per minute, hour or day, and says so above the curve ("Condensed: … shown as the average per …"). Choose a shorter time range or get the raw values through the export.
"Measurements dropped — reduce interval/tag count."
Storage cannot keep up with recording. Switch fast values to a cyclic recording mode or a longer interval, or record fewer values. See Statistics per value.
The storage range is running low
Shorten retention, record fewer values or store measurements in an external database. See Retention and storage.
Warning
When the storage medium is full, PlantBeat no longer stores anything and does not set a done flag for data records. The machine then waits instead of losing data records.
Data records do not arrive
- Not switched over yet: PlantBeat only records complete data records after Switch to records…. Otherwise the list in the wizard shows "Ring buffer set up – takes effect only after the switch-over".
- Read only: If the connection is set to "Read only", PlantBeat does not send a done flag. Data record reads with a done flag are then blocked.
- Not acknowledged: On the "Records" page, Not acknowledged counts the records that PlantBeat has stored but not yet reported back to the PLC. If the number keeps rising, check the connection and the done flag.
- Buffer overflow: The PLC has overwritten slots in the ring buffer that PlantBeat had not read yet. The message appears under Latest recording messages. You acknowledge it with Loss seen. Check the PLC program and turn on Overtake protection if needed.
See Data records.
Buffer/burst read returns no values
- The Target variable must be one of the selected variables of the connection. Otherwise PlantBeat does not read the field and does not set a done flag.
- "Record statistics" must be on for the target variable. Otherwise PlantBeat takes the values and sets the done flag, but stores none of them.
- If intermediate values are missing, the target variable is probably set to a cyclic recording mode. Then only one value per interval is kept. Choose "On change".
See Data records, section "Buffer/burst read for a fast variable". This method is deprecated. Set up new reads as a ring buffer.
Values of a line are missing on the master of a Federation (from version 1.11)
On the line, check under Pass on to master whether the value is ticked. Newly passed-on values apply from now on. The line does not send older data afterwards. See Share values.