S7-1200 and S7-1500 symbolic
PlantBeat reads S7-1200 and S7-1500 symbolically, that is, by the names of the variables, just like an operator panel (HMI). In the connection wizard, this is the "Symbolic" mode. It is the default for these CPUs.
What you need
- The PLC is reachable on the network, and port 102 is open.
- The access level of the CPU fits, see Prepare the PLC (TIA Portal).
- For a secured S7-1500 with firmware V2.9 or later, you also need the CPU password, see Secured S7-1500 with TLS.
That is all. You do not have to enable communication for remote partners, switch any block to "not optimized" or know any addresses. PlantBeat reads optimized blocks just like non-optimized ones.
What PlantBeat reads from the CPU
After "Test connection" and Next ›, the wizard shows the symbol tree of the CPU:
| Area | Read | Write |
|---|---|---|
| Data blocks, with the name from TIA Portal, for example "Linie1 (DB1)" | yes | yes |
| Bit memory | yes | yes |
| Inputs and outputs | yes | no |
| S7-1500 technology objects (positioning and speed axes) | yes | no |
Writing only works if the connection is not set to "Read only". PlantBeat writes via the controls on dashboards and via the done flag of a record fetch.
HMI-visible variables only
From version 1.11, the tree has the switch HMI-visible variables only. It hides values that are not "Visible in HMI engineering" or not "Accessible from HMI/OPC UA/Web API" in TIA Portal, for example internals of technology objects. Values you have already selected stay visible.
If a value you need is missing: turn off the switch, or set both checkboxes on the variable in TIA Portal and download the project. Then click Reload in PlantBeat.
If the program in the CPU changes
PlantBeat remembers the symbols of the CPU. If someone changed and downloaded blocks or variables in TIA Portal, open the connection with Edit, go to step 2 and click Reload. New variables then appear in the tree.