LEDs and button
The PlantBeat Box shows its state with two LEDs, without any computer or browser. With the button, you shut it down or reset the network and the device.
The two LEDs
The green LED stands for the device, the red one for the plant, meaning the connections to the PLCs.
Green: device
| LED | Meaning |
|---|---|
| off | no power |
| steady on | starting up |
| blinks slowly (1× per second) | everything is fine |
| blinks fast (5× per second) | fault, the cause is shown in the user interface |
Red: plant
| LED | Meaning |
|---|---|
| off | plant OK, values are coming in |
| blinks slowly (1× per second) | connection fault, no values |
| steady on | no connection set up yet |
Rule of thumb from the user interface: Green blinking = all good. Red off = plant running.
You also see the current state of both LEDs in the user interface on the page Diagnostics, card "Status LEDs". The meaning is shown there again as a table.
Tip
If the green LED blinks fast, open the page Diagnostics. The messages that currently apply are shown at the top, for example almost full storage.
Find the box in the control cabinet
If several boxes are mounted side by side, click Identify device on the page Diagnostics in the card "Status LEDs". The green and red LEDs then blink alternately and fast (5× per second). With Stop identifying, you switch this off again.
The button
What the button does depends on how long you hold it. The LEDs show the level reached. The action is only triggered when you release the button.
| Hold down | LEDs meanwhile | Effect on release |
|---|---|---|
| less than 2 s | The box shuts down in an orderly way. | |
| 2 to 5 s | nothing, protection against pressing too long by accident | |
| 5 to 15 s | green blinks fast | Network reset: both ports back to "Automatic (DHCP)" |
| 15 to 25 s | red blinks fast | Factory reset |
| 25 s or more | LEDs off | cancel, nothing happens |
Network reset
The network reset is the emergency exit if you can no longer reach the box after setting a wrong static address. Hold the button for 5 to 7 seconds until the green LED blinks fast, and release it before the red LED blinks. Both LAN ports then get their address via DHCP again. Connections, dashboards and recordings are kept.
The same reset is available in the user interface under Settings, area "System", card "Reset", button Network reset (both ports to DHCP).
Factory reset
Caution
The factory reset deletes the connections, dashboards, recordings and users of the box. License and registration are kept. Back up the configuration first, see Data backup.
The factory reset also sets both LAN ports to DHCP. A static address is gone afterwards. Then open the box at http://plantbeat.local.
After the factory reset, the box restarts and shows the initial setup again. You then create the first administrator as you did the first time, with the setup code from the label. The code stays valid, the factory reset does not change it.
If your box has no setup code on the label, a factory reset with the button opens the initial setup for 30 minutes without a code. A factory reset from the user interface does not open this window.
In the user interface, the factory reset is under Settings, area "System", card "Reset". To confirm, type the word WERKSRESET and click Run factory reset.