Operations checklist

Updated: from version 1.11

Go through this list once before production use and tick off what is done. Most items only take a few minutes.

Network

  • The machine network with the PLCs is separated from the company network. The Box is connected to each network with one port. A Windows computer has two network cards.
  • The firewall only allows TCP 102 (Siemens) or TCP 48898 (Beckhoff) to the PLCs, and everything else only to the destinations listed under Firewall rules.
  • Beckhoff connections only run on an isolated machine network.
  • The Box has a reachable time server, see Language and time.

Access

  • Access protection is switched on. The bar "This device is not protected by a sign-in." no longer appears.
  • Each person has their own account with a suitable role. Only those who need to configure the system are administrators. See Users and roles.
  • "Allow viewing without signing in" is only on if a shop floor monitor should show content without sign-in.
  • Custom DNS names of the installation are listed under "Additional host names".
  • The type plate with the setup code has not been photographed for or passed on to third parties.

Writing to the PLC

  • PLCs that are only observed are set to Read only.
  • For critical values, "Confirm before writing" is turned on for the tile.
  • A dashboard for the shop floor monitor has no write tiles. Switches, setpoints and similar elements can still be operated in wall mode.

Secured PLCs

  • For secured S7-1500, the CPU password is stored in the connection and the PLC certificate is confirmed. See Secured S7-1500 with TLS.
  • The "Evidence report" on the Connections page has been created and filed, if your audit requires it.

HTTPS

  • On the Box, encrypted access is set up under Settings, section "Access & security", card "Secure connection (HTTPS)". It is required for the Federation and the interface (API) on the Box.
  • To avoid the browser warning on the first visit, upload a certificate as a PFX file under Use your own certificate.
  • Encrypted access only is only switched on after access over https:// has worked.
  • Step by step: Secure connection (HTTPS).

Data

  • Retention matches your requirements, see Retention and storage.
  • On Windows, the data directory is secured, and the Diagnostics page shows no "SECURITY" notice. See Data directory.
  • An external data storage uses a verified, encrypted connection ("Transport security").
  • API access entries have an expiry date and only the lines they need. Access entries that are no longer needed are revoked.

Operation

  • Updates are installed as soon as PlantBeat reports them, automatically within a time window if you want. See Updates.
  • A current backup is stored outside the device, and the passphrase separately from it.
  • E-mail sending has been checked with a test e-mail so that alarms arrive.