Operations checklist
Go through this list once before production use and tick off what is done. Most items only take a few minutes.
Network
- The machine network with the PLCs is separated from the company network. The Box is connected to each network with one port. A Windows computer has two network cards.
- The firewall only allows TCP 102 (Siemens) or TCP 48898 (Beckhoff) to the PLCs, and everything else only to the destinations listed under Firewall rules.
- Beckhoff connections only run on an isolated machine network.
- The Box has a reachable time server, see Language and time.
Access
- Access protection is switched on. The bar "This device is not protected by a sign-in." no longer appears.
- Each person has their own account with a suitable role. Only those who need to configure the system are administrators. See Users and roles.
- "Allow viewing without signing in" is only on if a shop floor monitor should show content without sign-in.
- Custom DNS names of the installation are listed under "Additional host names".
- The type plate with the setup code has not been photographed for or passed on to third parties.
Writing to the PLC
- PLCs that are only observed are set to Read only.
- For critical values, "Confirm before writing" is turned on for the tile.
- A dashboard for the shop floor monitor has no write tiles. Switches, setpoints and similar elements can still be operated in wall mode.
Secured PLCs
- For secured S7-1500, the CPU password is stored in the connection and the PLC certificate is confirmed. See Secured S7-1500 with TLS.
- The "Evidence report" on the Connections page has been created and filed, if your audit requires it.
HTTPS
- On the Box, encrypted access is set up under Settings, section "Access & security", card "Secure connection (HTTPS)". It is required for the Federation and the interface (API) on the Box.
- To avoid the browser warning on the first visit, upload a certificate as a PFX file under Use your own certificate.
- Encrypted access only is only switched on after access over
https://has worked. - Step by step: Secure connection (HTTPS).
Data
- Retention matches your requirements, see Retention and storage.
- On Windows, the data directory is secured, and the Diagnostics page shows no "SECURITY" notice. See Data directory.
- An external data storage uses a verified, encrypted connection ("Transport security").
- API access entries have an expiry date and only the lines they need. Access entries that are no longer needed are revoked.
Operation
- Updates are installed as soon as PlantBeat reports them, automatically within a time window if you want. See Updates.
- A current backup is stored outside the device, and the passphrase separately from it.
- E-mail sending has been checked with a test e-mail so that alarms arrive.