Language and time
Language
PlantBeat is available in German and English. Anyone can switch at the bottom of the left sidebar with DE or EN.
Administrators also find the choice under Settings, area "General", card "Language", with German or English.
The choice applies to your browser. A colleague on another computer can use the same installation in the other language. Without a choice, PlantBeat follows the language setting of the browser.
Time
The correct time matters: measured values, alarms and data records carry a timestamp, and the license checks the clock. The card "Time" is under Settings, area "General".
Note
On Windows, PlantBeat does not set the system clock. The card shows "Set the clock in Windows" there. You correct the time zone and time in the Windows settings.
What the card shows
- Current time and Time zone of the box,
- Time synchronized: yes, or why not, for example "no — time server not reached",
- Deviation from the license server, as soon as the box has measured it.
Set the time zone and time server
- Choose the Time zone, for example Europe/Berlin.
- Leave Synchronize time automatically ticked.
- If needed, enter your own Time server entries, several separated by semicolons. Empty means: the system default.
- Click Apply.
The application restarts briefly, and the page is unavailable for a moment.
Tip
If the card says "Synchronization is running but has not reached a time server yet", check internet access, name resolution (DNS) and that time synchronization (NTP, UDP 123) is allowed. In a plant network without internet, enter the time server of your plant.
Set the clock by hand
If time synchronization does not work, for example after a power failure in a network without a time server, set the clock by hand under Set the time:
- Check the suggested New time. The suggestion is the time of your browser.
- Click Set clock and confirm the prompt.
Setting the clock by hand only works while time synchronization is not in sync. When synchronization is running, it sets the clock itself.
Warning
If the new time differs from the clock of the box by more than one day, PlantBeat warns you. A clock set too far ahead locks out the real PLCs as soon as it is set correctly again. A clock set back before the last seen point in time keeps the real PLCs disconnected.
Clock from the license server
If the box has no working time synchronization but has a connection to license.plantbeat.io, it sets its clock to the time of the license server. The card reports this, and the jump appears in the event history.
If the clock is so far off that the license is no longer valid, the notice bar at the top shows the reason and the button Set the time. How to get a clock release without internet is described under Activate the license.