Share values

Updated: from version 1.11

The line always decides what the master gets from it and what the master may do there. The master never changes the settings of a line. You set everything on the line under Settings, section "Data", card "Federation", as an administrator.

Pass on to master

Under Pass on to master there is a checkbox for each value and each data record model. By default, all are checked, and new values and models are included automatically ("New values and models are passed on automatically.").

  • If you clear a checkbox, the master stops getting this value from now on.
  • If you check a box again, it applies from now on. The line does not send older data of this value afterwards.
  • Values that are neither recorded nor a field of a data record cannot be passed on. They show "not passed on (neither recorded nor a data record field)".
  • If an alarm rule is attached to a value and you exclude the value, the card warns you: New alarms of this rule no longer appear on the master.

For data records, sources and models are linked. If you exclude a model, its sources are not passed on either, and vice versa. The card names every such case, for example "Source "…" is not passed on because it is a station of the excluded model "…"."

Access from the master

Under Access from the master, you choose what a user on the master may do on this line. The setting applies to access to the line, not to the data: Whatever is checked under Pass on to master, the line sends with every setting. Anything the master should not get, you exclude there.

Setting Meaning The master shows
View only The master may view the line but not operate anything. This is the default. "The line allows the master to view only."
View and operate The master may also write the values you check under Operable from the master. "The line allows the master to view and operate."
Off The master may do nothing on the line, not even view. "The line has switched off access from the master."

Operable from the master

If Access from the master is set to "View and operate", the list Operable from the master appears. You can choose from the recorded values that are passed on. The master may only write the checked ones. By default, none are checked.

Operating from the master only works if all of these are true:

  • The line is set to "View and operate", and the value is checked under Operable from the master.
  • Access protection is on at the master, and the user is signed in with at least the Operator role.
  • The line runs PlantBeat 1.11 or newer. Otherwise the master shows "Operating from the master needs PlantBeat 1.11 or newer on the line."
  • The master has a valid "PlantBeat Master" license. Otherwise it shows "Without a master license this master does not operate any line."
  • The line is paired. The master only displays a decoupled line ("The line is decoupled – view only.").
  • The line delivers data. If it has delivered nothing for 90 seconds, the master locks the tile and gives the reason.

Every operation is logged on the line, with user and master.

Warning

If a tile on the master shows "Status unknown – check on the line", the line's response did not arrive in time. The line may already have written the value. Check the line's log before you repeat the operation.

Next steps