PLC connection

Updated: from version 1.11

The connection stays "Disconnected"

  • Check the IP address of the PLC with a ping from the same network.
  • Check that port 102 is open between PlantBeat and the PLC (Beckhoff: TCP 48898).
  • The message "No connection to … Check ping, protection level/password and port 102." means: the PLC does not respond.
  • For Beckhoff: check the route on the PLC, the AmsNetId and the AMS port, see Beckhoff TwinCAT 3.
  • If there is a license notice bar at the top, PlantBeat does not connect to real PLCs. See License.

"Stopped after 5 reconnect attempts"

The PLC could not be reached for a longer time. After that, PlantBeat tries again every minute on its own and continues recording as soon as the PLC responds. If the message stays, check the IP address, the network and port 102.

The PLC asks for a password

Message Remedy
"Recording stopped – the PLC requires a password (edit the connection and enter the password)." The CPU has an access level with a password. Open the connection on the Connections page with Edit and enter the CPU password.
"Recording stopped – the PLC rejected the password (edit the connection and check the password)." The password is wrong. PlantBeat stops immediately so that no further failed sign-ins occur on the CPU. Check the password and enter it again.

A secured S7-1500 no longer records

In most cases, the certificate of the CPU has changed. Check and confirm the new certificate in the "PLC certificate" window on the Connections page. With the option "Keep recording after a certificate change until confirmed", recording continues for the configured transition period. See Secured S7-1500 with TLS.

Variables are missing when reading them in

  • Check the CPU type and mode: S7-1200 and S7-1500 in "Symbolic" mode, S7-300, S7-400 and LOGO! 0BA8 in "Legacy" mode. See Prepare the PLC (TIA Portal).
  • If only some are missing, check the "HMI-visible variables only" switch in the "Variables" step of the connection wizard. The switch hides variables that are not "Visible in HMI engineering" or not "Accessible from HMI/OPC UA/Web API" in TIA Portal.
  • If a value is missing that you only created in the PLC later, open the connection with Edit and go back to step 2 with Back.

A write element in the dashboard does not respond

  • Writing requires at least the Operator role.
  • If the connection is set to "Read only", PlantBeat does not write.
  • If "Confirm before writing" is turned on for the tile, confirm the prompt.
  • On the master of a Federation: the line must allow operation, see Share values.

Practice machine for comparison

Create a connection with the IP address demo. If it runs, PlantBeat and the user interface are fine, and the fault lies between PlantBeat and the real PLC: network, firewall or CPU settings. See Demo line.