Secured S7-1500 with TLS
A secured S7-1500 with firmware V2.9 or later requires an encrypted connection (TLS). PlantBeat sets it up automatically. There is no switch for it. You only enter the CPU password and confirm the CPU certificate once.
Create the connection
- In the connection wizard, choose the manufacturer Siemens S7, CPU type S7-1500 and mode "Symbolic".
- Under Password (optional), enter the password of the access level PlantBeat should use.
- Click Test connection. PlantBeat fetches the CPU certificate. If it has not been confirmed yet, the "PLC certificate" window opens automatically.
- Check and confirm the certificate (next section). If you closed the window, reopen it with PLC certificate ….
- Select the variables with Next › and save with Save & continue.
If the password is missing or wrong, PlantBeat tells you clearly. With a wrong password, recording stops immediately so that no further failed logins occur on the CPU.
In "Legacy" mode, a connection is never encrypted and has no certificate. For a secured S7-1500, always use "Symbolic".
Confirm the PLC certificate
PlantBeat checks the CPU certificate before it sends the CPU password. This way, the password only goes to the right PLC.
The "PLC certificate" window shows Subject, Issuer, Valid, Fingerprint SHA-256 and Key SHA-256 (SPKI).
- Compare the fingerprint with TIA Portal or the display of the CPU.
- If it matches, click Confirm certificate.
Only then does PlantBeat connect with the password. Only an administrator can confirm. In the connection list, the "PLC certificate" badge shows the status.
Caution
If access protection is off, anyone on this device can confirm certificates. Turn on access protection under "Settings".
If the certificate changes
If someone renews the CPU certificate, recording stops by default. PlantBeat then sends no password until you check and confirm the new certificate. The connection list shows this in the row of the connection.
In the "PLC certificate" window you can change this behavior per connection:
| Option | Effect |
|---|---|
| Keep recording after a certificate change until confirmed | Recording continues for the set transition period, 1 to 7 days at most ("Transition at most (days, 1–7)"). After that, it stops until confirmed. |
| Pre-approve an announced change for 24 h | For a planned renewal in TIA Portal: the first new certificate within 24 hours is accepted without a stop and logged. |
| Do not check the certificate of this connection (e.g. test CPU) | No confirmation and no warning on a change. Intended for test PLCs only. |
Warning
During the transition period, the login and CPU password go to a remote station that has not been confirmed. If an attacker sits in between, the password is exposed. Only use the transition period if you know why the certificate changed.
If a CPU suddenly answers unencrypted although it was encrypted before, recording also stops. This can be an attack. Only confirm it with Continue unencrypted (confirm downgrade) if encryption was deliberately turned off in TIA Portal.
PlantBeat warns you 30 days and 7 days before a certificate expires.
Evidence report
On the "Connections" page, the Evidence report button opens a report on the certificates of all PLCs in the browser. You print it as a PDF from the browser, for example for an audit. Only administrators see the button. The report counts demo connections as simulations.
After the update to 1.11
Existing secured S7-1500 connections keep recording after the update until someone confirms the certificate. Please check and confirm the certificate for every secured connection.