E-mail notification
PlantBeat sends alarms, all-clears, maintenance and drift messages by e-mail. The e-mails go out directly from your PlantBeat through your own mail server. There is no PlantBeat mail server or cloud service for this. You enter the mail server once, as an Administrator.
What you need from your IT
| Item | Note |
|---|---|
| Address of the mail server (SMTP) | name or IP address, for example 192.0.2.25 |
| Port | usually 587 with STARTTLS or 465 with SSL |
| Encryption | None, STARTTLS or SSL |
| User name and password | a mailbox or service account for PlantBeat, if the server requires sign-in |
| Sender address | an address of your company from which PlantBeat may send |
PlantBeat must be able to reach the mail server over the network. If the server is outside your plant network, the firewall must allow the connection from PlantBeat to the mail server on the selected port.
Enter the mail server
- Open "Settings" › "Notifications". The card is called "E-mail dispatch (SMTP)".
- Fill in the fields:
| Field | Meaning |
|---|---|
| Server | address of the mail server |
| Port | port of the mail server |
| Encryption | "None", "STARTTLS" or "SSL" |
| User name, Password | sign-in to the mail server. If a password is already stored, leave the field empty so it is not changed. |
| Sender address, Sender name | how PlantBeat appears in the recipients' mailbox |
| Global recipients | e-mail addresses, separated by semicolons (;). They apply to every rule without recipients of its own. |
- Click Save and send test e-mail. PlantBeat saves and sends an e-mail with the subject "PlantBeat test e-mail" to the global recipients.
- If "Test e-mail sent." appears, check the mailbox. If "Test e-mail failed: …" appears, the text gives the reason.
The Save and send test e-mail button stays disabled until at least one global recipient is entered. Save stores the settings without a test e-mail.
Tip
The test e-mail does not arrive? Check the spam folder first. Then check port and encryption: 587 usually goes with STARTTLS, 465 with SSL. If the server rejects the sign-in, ask your IT whether the account may send e-mail over SMTP.
Who gets which e-mail
- Every rule, every maintenance counter and every drift rule has its own "Recipients" field.
- If it is empty, the e-mails go to the global recipients.
- Separate several addresses with semicolons, for example the address of the shift supervisor and that of the maintenance team.
Without a mail server
You can also use PlantBeat without a mail server. Alarms, notices, maintenance and drift messages are still created and appear in the history under "Alarms", with the remark "ohne Mail – kein Mailserver eingerichtet" (no e-mail, no mail server set up).
When an e-mail is not delivered
If an e-mail cannot be delivered, for example because the server rejects it, cannot be reached, does not answer in time or no valid recipient is entered, PlantBeat writes the message with the type Send failure to the history. You find it under "Notifications" in the "Event history" and under "Alarms" in the history. The alarm itself is not lost: it still appears under "Open alarms".