Clock and clock code
The correct time matters: measurements, alarms and data records carry a timestamp, and the license checks the clock.
The time is wrong
- Box: Under Settings, section "General", card "Time", check that time synchronization is active and that the time server can be reached (NTP, UDP 123). If needed, enter your plant's time server.
- Box without a time server: As long as time synchronization is not active, you set the clock by hand with Set the time. If the Box can reach
license.plantbeat.io, it sets its clock to the time of the license server. - Windows: PlantBeat does not set the system clock. The card shows "Set the clock in Windows". Correct the time zone and time in the Windows settings.
See Language and time.
The PLCs are disconnected after a clock jump
If the clock was set back, for example after a power failure without a time server or by hand, the license blocks the real PLCs. The notice bar at the top names the reason and shows the Set the time button. Demo connections and the user interface stay usable.
To get the PLCs back:
- Set the clock correctly, as described above.
- With internet: If the device can reach
license.plantbeat.io, PlantBeat gets the clock release automatically. You don't need to do anything else. - Without internet: Use the clock code, see below.
Warning
Don't set the clock too far ahead. A clock set too far ahead blocks the real PLCs as soon as it is set correctly again. If the new time differs from the clock of the Box by more than one day, PlantBeat warns you first.
Clock release with the clock code
Without internet, a clock release from support helps. As an administrator, do the following:
- First set the device time correctly.
- Open Settings, section "System", card "Siemens driver license". There you find Clock code for support.
- Click Create clock code.
- Give the code to support, through the support form or by e-mail to [email protected]. The code is valid for 7 days and can be used once.
- Support sends you a file with the extension
.zeit. Import it in the same card under Import update entitlement or clock release.
After that, PlantBeat connects to the real PLCs again. If the card shows "The clock is considered correct again. A clock code is no longer needed.", the block was already lifted before, for example because the release came online.
| Message | Meaning |
|---|---|
| "First set the device clock correctly, then create the clock code and give it to support." | No code has been created yet. |
| "Give this code to support. It is valid for 7 days and can be used once. …" | The code is ready. |
| "The clock code could not be created. Please try again later." | Temporary error. Try again later. |
On the master of a Federation: "Clock of the line is off by …"
The clock of a line is off by more than 2 minutes. Give the line a time server. See Operation and messages.