Network behavior

Updated: from version 1.11

All connections are initiated by PlantBeat. The only exceptions are access to the user interface itself and, if you set them up, receiving data in the Federation and the interface (API). This section describes when PlantBeat opens which connection. The ports are listed as a table under Firewall rules.

To the PLCs

PLC Connection When
Siemens S7 TCP 102 Continuously, while data is being collected
Secured S7-1500 (firmware V2.9 or later) TCP 102 with TLS Continuously, while data is being collected
Web server of the S7 HTTPS 443 to the CPU Only if "Texts as in TIA Portal" is set up in the diagnostic buffer
Beckhoff TwinCAT 3 ADS over TCP 48898 Continuously, while data is being collected
  • Reading: PlantBeat reads S7-1200 and S7-1500 symbolically, just like an HMI. It reads S7-300, S7-400 and LOGO! 0BA8 through addresses that you create once. PlantBeat does not change anything in the PLC program and does not download anything to it.
  • Writing: only in two cases that someone sets up deliberately: operating elements in the dashboard (switch, setpoint, push button and others) and the done flag of a data record read. Every operation is logged with user, variable and value.
  • Read only: If a connection is set to "Read only", PlantBeat sends no write command to this PLC, not even a done flag.
  • Secured S7-1500: PlantBeat checks the certificate of the CPU before it sends the CPU password. See Secured S7-1500 with TLS.
  • Beckhoff: Without an installed TwinCAT, PlantBeat uses a built-in ADS router without ADS Secure. For this reason, run Beckhoff connections on an isolated machine network. See Beckhoff TwinCAT 3.

To the license server and download

Destination When What is transferred
license.plantbeat.io, HTTPS 443 Once during license activation Order token and hardware identifiers that the license is bound to
license.plantbeat.io, HTTPS 443 Regularly, hourly by default Update check with the running version, the Box also with its serial number
license.plantbeat.io, HTTPS 443 When needed Update entitlement ("Updates until …") and clock release
download.plantbeat.io, HTTPS 443 Only when an update is pending The update package

If the Box has no working time synchronization, it sets its clock to the time that the license server sends along. PlantBeat checks the license itself locally using its signature. No connection is needed for that.

Only if you turn it on

Function Destination What is transferred
E-mail sending Your mail server, SMTP (typically port 587 with STARTTLS) E-mails about alarms, maintenance and reports to your recipients, with measurements
External data storage Your database server Measurements and data records. Default ports: SQL Server 1433, PostgreSQL 5432, MySQL / MariaDB 3306
Federation (on the line) The master, HTTPS 443 (Box) or 5211 (Windows) The shared values, alarms and data records of the line
Connection to a cloud analytics service gateway.smartlifebi.com, HTTPS/WSS 443 Only the shared data sources, only on request
Crash reports (off by default) license.plantbeat.io, HTTPS 443 Product, version, hash of the hardware identifier, error message. Not anonymous
Usage data (off by default) license.plantbeat.io, HTTPS 443 Random usage ID and usage figures, no variable names and no values
Remote support access (Box only) tunnel.plantbeat.io, SSH TCP 2222 Encrypted tunnel for the duration you allow
Map widget in the dashboard tile.openstreetmap.org, HTTPS 443 Map images, fetched by the browser, not by PlantBeat

Note

PlantBeat AI runs entirely on the Box. Questions and answers do not leave the device.

System services of the Box

The PlantBeat Box also queries its time server (NTP, UDP 123) and the DNS server of its network. By default, it gets its address through DHCP. It announces plantbeat.local on the local network through mDNS (UDP 5353).

Incoming

  • Windows: By default, the user interface only listens on the computer itself at http://localhost:5210 (you can change the port in the setup). It cannot be reached from the network. Only when you run the installation as a Federation master or create an API access entry does PlantBeat also open HTTPS port 5211 after a restart.
  • Box: By default, a packet filter is active. Only the user interface over HTTP 80 and HTTPS 443 (also for the API and the Federation), plantbeat.local and ping can be reached. The maintenance access can only be reached from private networks. Port 5210 on the Box can only be reached internally. Secure connection (HTTPS) describes how to set up encrypted access.

The Box does not forward traffic between its two LAN ports.

Next steps